LaserCOMPACT Specifications
Supply Voltage: 18 to 30VDC
Power Consumption:
5.4W quiescent, 5.9W with alarm
Current Consumption:
225mA quiescent, 245mA with alarm
Fuse Rating: 1.6A
Dimensions (WHD):
225mm x 225mm x 85mm
(8 7/8” x 8 7/8”x 3 3/8”)
Weight: 1.9kg (4.2lbs.)
Operating Temperature:
Detector Ambient -10°C to 39°C (14°F to 103°F)
Sampled Air -20°C to 60°C (-4°F to l40°F)
Sampling Network:
Maximum area of Coverage 800sq.m (8000sq.ft)
Maximum Pipe lengths:
1 x 80m
2 x 50m
Computer Design Tool: ASPIRE™
Pipe:
Internal Diameter 15-21mm (9/16” - 7/8”)
External Diameter 25mm (1”)
Relays:
3 Relays rated 2A @ 30VDC
Default Configuration
Fire
Pre-Alarm
Alert/Fault (Maintenance & Isolate)
Programmable 0 - 60 seconds time delay for each relay
Software Programmable Relays:
Latching or non-latching
IP Rating: IP30
Cable Access:
4 x 25mm (1”) cable entries
Cable Termination:
Screw Terminal blocks 0.2-2.5sq mm (30-12 AWG)
Sensitivity Range:
0.005 to 20% obs/m
(0.0015 to 6% obs/ft)
Threshold Setting Range:
Alert: 0.005 - 1.990% obs/m
(0.0015-0.6218% obs/ft)
Pre-Alarm: 0.010-1.995% obs/m
(0.0031-0.6234% obs/ft)
Fire: 0.015-20.00% obs/m (0.0046-6.25% obs/ft)*
*Limited to 4% obs/ft for UL
Software Features:
Event log: Up to 12,000 events stored on FIFO
Smoke level, alarms and faults with time and date stamp
AutoLearn: Minimum 15 minutes, maximum 15 days.
Recommended minimum 14 days. During AutoLearn thresholds are NOT changed from pre-set values.
Configurable General Input (24VDC):
Standby, Mains OK and Reset/Isolate
Ordering Information:
VLC-505 VESDAnet Version (VN)
VLC-500 Relays only Version (RO)
|