VESDA LaserSCANNER Features
The LaserSCANNER Display
The LaserSCANNER display has a bar graph to indicate the overall smoke level, alarm threshold and fault indication. The bar graph displays the individual sector smoke levels during the scanning sequence. There is an extra LED to indicate that a First Alarm Sector (FAS) has been identified and an extra function to the Silence Button to allow for Manual Scan to be initiated.
The LaserSCANNER display module can be mounted into the LaserSCANNER front cover or remotely into a 19in subrack or a Remote Box.
Relay Options
The LaserSCANNER detector can be fitted with a programmable 7 or 12 relay Termination card. The additional Relays on the 12 way Termination card may be assigned on a "per sector" basis. Relays may be mounted in a remote box or in a 19in subrack.
AutoLearn™ and Referencing
The LaserSCANNER has both the AutoLearn™ and Referencing software functions to ensure optimum operation in different environments and to eliminate the occurrence of nuisance alarms.
AutoLearn monitors the ambient environment and sets the most appropriate alarm thresholds (Alert, Action, Fire 1, Fire 2) during the commissioning process.
Referencing ensures external pollution to a protected environment does not interfere with the true smoke level being detected.
Additional Features
- Individual Pipe Identification
- Adaptive Scan Threshold
- Wide Sensitivity Range
- Laser Based Smoke Detection
- VESDAnet™ Communication
- 4 Alarm Levels per Sector
- High Efficiency Aspirator
- Dual Stage Air Filter
- Easy to Replace Air Filter
- 7 or 12 Programmable Relays Option
- Event Log
- Recessed Mounting
|