Multi-function Card Specification

Dimensions

Length x Width x Height
110 mm (41/3”) x 70 mm (2 3/4”) x 20 mm (13/16”)

Weight
0.08 kg (0.176 lb)

Terminals
0.2 - 2.5 mm2 (30-12 AWG)

Electrical Ratings

Power consumption
1 W from the detector at 24 VDC (less than 42 mA)

Relay outputs
2 A at 30 VDC

MPO input power supply
24 VDC (21–30 VDC) (VIC-030 only)

MPO input current
100 mA more than MPO output load (VIC-030 only)

MPO output current
1 A (maximum) (VIC-030 only)

End of line resistor (MPO & GPI)
2.7K Ohm

Operating Conditions

Detector ambient temperature
0 to 40°C (32 to 104°F)

Humidity
5% to 95% (non-condensing)

Detector Compatibility
Supports VLF-250 and VLF-500

Input/Output Assignments

VIC-020
Output for Relay 1:
ALERT (follows latching configuration of VLF ALERT status)
Output for Relay 2:
FIRE-2 (follows latching configuration of VLF FIRE-2 status)

Input for GPI: FAULT
GPI reports status on following conditions:
- EOL > No fault
- Short > Fault # 115/IFF6
- O/C > Fault # 111/IFF8

VIC-030
Output for Relay 1:
ALERT (follows latching configuration of VLF ALERT status)
Output for Relay 2:
FIRE-2 (follows latching configuration of VLF FIRE-2 status)
MPO:
ALERT (unless disabled) (follows latching configuration of VLF ALERT status)

 