| Type |
2A LaserPLUS & LaserSCANNER |
1.5A LaserCOMPACT |
5A Multiple Modules |
| Input |
230VAC (+10% -15%) factory default setting 110VAC (+10% -15%) field selectable option |
230VAC (+10% -15%) factory default setting; 110VAC (+10% -15%) auto configuring |
| Power output |
18-29 VDC 1.9 Amps continuous 2 Amps at 25 C |
18-29 VDC 1.5 Amps continuous |
18-29 VDC 5.0 Amps continuous |
| Load |
18-29 VDC 0.5 Amps continuous 1.9A Short Duration (Ref EN54-4) |
18-29 VDC 0.5 Amps continuous 1.5A Short Duration (Ref EN54-4) |
18-29 VDC 1.2 Amps continuous 5A Short Duration (Ref EN54-4) |
| Dimensions (HxWxD) |
225 x 350 x 105.2 |
225 x 285 x 115.2 |
351 x 451 x 185 |
| Weight |
3.6 Kg (without batteries) 14.2 Kg (with max. batteries) |
2.95 Kg (without batteries) 8.25 Kg (with batteries) |
7 Kg (without batteries) 34.86 Kg (with max. batteries) |
| Temperature |
-5 to +40 C ambient |
| Humidity |
10-95% RH non-condensing |
| IP Rating |
IP 30 |
| Batteries (Not supplied by VF&S) |
Either: 2 x 12V, 7Ah or:2x12V,12Ah or:4x12V,7Ah |
2 x 12V, 7Ah |
Either: 2 x 12V, 24Ah or:2x12V,38Ah |
| Indications |
OK -green LED Fault -yellow LED Internal and External |
OK -green LED Fault -yellow LED Internal only |
OK -green LED Fault -yellow LED Internal and External |
| Fault Relay |
Change-over NO-COM-NC 2A @ 30VDC |
| Fuse Rating |
Input -3.15A Non Serviceable Battery fuse -3.15A Current limiting -2A |
Input -3.15A Non Serviceable Battery fuse -3.15A Current limiting -2A |
Input -3.15A Non Serviceable Output-4x2A Slow Blow 1 x 10A Battery fuse |
| Cable Entries |
5 off 25mm knockouts Various positions to match LaserPLUS |
4 off 25mm knockouts Various positions to match LaserCOMPACT |
7 off 20mm knockouts Various positions to match |
| Finish |
Power Coat Semi-Gloss |
Powder Coat Semi-Textured |
| Colour |
Light grey -Ral 9018 |
Light grey -Ral 7035 |
| Mounting |
4 x 5.5mm holes on 318 x 175 centres |
4 x 5.5mm holes on 243 x 175 centres |
4 x 5.5mm holes on 418 x 300 centres |
| Part number |
VPS-220 |
VPS-215 |
VPS-250 |