Remote Display Specifications

Supply Voltage: 18 to 30VDC

Power Consumption @ 24VDC:

 
Module Only
In Remote Mounting Box
(No Relays)
 
Quiescent
With Alarm
Quiescent
With Alarm
Power
1.6W
2.2W
2.4W
3.0W
Current
60mA
80mA
90mA
110mA

Dimensions (WHD):
Mounted in Remote Box -140 mm x 150 mm x 85 mm (5.5 in x 5.9 in x 3.4 in)

Operating Temperature:
0° to 39°C (32° to 103°F)Humidity: 10-99% RH non-condensing

Alarm Indicators:
High Intensity LEDs with 70 degree viewing angle

Push Buttons Keys: (Mode/Test, Silence/Scan, Reset, Isolate)
Can be disabled during commissioning (except Silence). A pressed key gives a short tone when enabled and a long tone when disabled.

Mode/Test (Dual Function):
Short press: Selects modes on the numeric display: Sensitivity, Smoke Level, and Zone Number. For LaserSCANNER displays, the First sector/pipe in alarm can be selected. Note: The current mode is indicated by the appropriate LEDs.
Long press: Activates the Test Mode

Silence (Silence/Scan): (Dual function on SCANNER only)
Short press: Silences any alarm or fault warnings.Flashing LEDs are permanently lit until the event is cleared and the system reset. Only affects the local display.
Long press: Initiates the scanning of each pipe individually for smoke and displays the current levels.

Reset: Resets all the alarms and faults on the detector and its associated displays. If the alarm or fault condition has not been cleared then the appropriate fault indications will be repeated. Reset does not clear the isolate mode.

Isolate: Isolates the detector from any external devices or systems. This includes all the relays in the detector and in remote units. Isolate relay is activated while the detector is in isolate mode

Fault Indicators:
System: A fault that affects the whole VESDA system (any devices connected on VESDAnet)
Zone: A fault that affects only the assigned VESDA detector and its associated displays.
Urgent: A serious fault that requires immediate attention. This light will only illuminate when at least one other fault light is lit.
Power: A fault with either the mains AC or battery backup power supply.
Network: A failure in the VESDAnet communications link.
Airflow: Airflow drift. Urgent indicates serious aspirator or pipe failure.
Filter: Filter needs replacing. Urgent indicates that filter replacement is overdue.

 

Download Data Sheet